Mitsubishi Heavy air conditioner indicator lamps and blink codes

Many units show a fault only by blinking lamps. Find the pattern you see, then open the code.

CodeHow it showsMeaning
0RUN light: OFF
TIMER light: OFF
RUN light (10's digit): OFF
TIMER light (1's digit): OFF
Normal
01RUN light (10's digit): OFF
TIMER light (1's digit): 1-time flash
Error of wired remote control wiring (When wired remote control was connected) (When…
05RUN light (10's digit): OFF
TIMER light (1's digit): 5-time flash
Can not receive signals for 35 seconds (if communications have recovered)
11RUN light: 1 time flash
TIMER light: 1 time flash
Occurrence conditions: Compressor start fails 42 times in succession and the reason for the final failure is current cut
Error display: yes (2 times)
Start of compressor program
12RUN light: 1 time flash
TIMER light: 2 time flash
RUN lamp (tens place): Flash 1 time
TIMER lamp (ones place): Flash 2 times
Below 20 rps
13RUN light: 1 time flash
TIMER light: 3 time flash
RUN lamp (tens place): Flash 1 time
TIMER lamp (ones place): Flash 3 times
Over 20 rps
14RUN light: 1 time flash
TIMER light: 4 time flash
RUN lamp (tens place): Flash 1 time
TIMER lamp (ones place): Flash 4 times
Over voltage (DC350V)
15RUN light: 1 time flash
TIMER light: 5 time flash
RUN lamp (tens place): Flash 1 time
TIMER lamp (ones place): Flash 5 times
Short circuit of power transistor (high voltage side)
16RUN light: 1 time flash
TIMER light: 6 time flash
RUN lamp (tens place): Flash 1 time
TIMER lamp (ones place): Flash 6 times
Power cut, loop failure
17RUN light: 1 time flash
TIMER light: 7 time flash
Software current cut
21RUN lamp (tens place): Flash 2 times
TIMER lamp (ones place): Flash 1 time
Abnormal result of PWM algorithm
22RUN light: 2 time flash
TIMER light: 2 time flash
RUN lamp (tens place): Flash 2 times
TIMER lamp (ones place): Flash 2 times
Input below 2A (PWM above 90%)
23RUN light: 2 time flash
TIMER light: 3 time flash
Occurrence conditions: When an abnormal stop occurs 3 times with automatic recovery within 20 minutes after the outdoor unit's power supply was turned on
RUN lamp (tens place): Flash 2 times
3 abnormal stops within 20 min
27RUN light: 2 time flash
TIMER light: 7 time flash
Error display: yes (3 times)
RUN lamp (tens place): Flash 2 times
Error of outdoor fan motor (for DC motor only)
28RUN light: 2 time flash
TIMER light: 8 time flash
RUN lamp (tens place): Flash 2 times
TIMER lamp (ones place): Flash 8 times
Different voltage
29RUN light: 2 time flash
TIMER light: 9 time flash
RUN lamp (tens place): Flash 2 times
TIMER lamp (ones place): Flash 9 times
Low voltage
31RUN light: 3 time flash
TIMER light: 1 time flash
RUN lamp (tens place): Flash 3 times
TIMER lamp (ones place): Flash 1 time
Cooling safe current I
32RUN light: 3 time flash
TIMER light: 2 time flash
RUN lamp (tens place): Flash 3 times
TIMER lamp (ones place): Flash 2 times
Heating safe current I
33RUN light: 3 time flash
TIMER light: 3 time flash
RUN lamp (tens place): Flash 3 times
TIMER lamp (ones place): Flash 3 times
Cooling safe current II
34RUN light: 3 time flash
TIMER light: 4 time flash
RUN lamp (tens place): Flash 3 times
TIMER lamp (ones place): Flash 4 times
Heating safe current II
35RUN light: 3 time flash
TIMER light: 5 time flash
RUN light (10's digit): 3-time flash
TIMER light (1's digit): 5-time flash
Cooling high pressure control
36RUN light: 3 time flash
TIMER light: 6 time flash
RUN light (10's digit): 3-time flash
TIMER light (1's digit): 6-time flash
Compressor overheat 110°C
37RUN light: 3 time flash
TIMER light: 7 time flash
RUN light (10's digit): 3-time flash
TIMER light (1's digit): 7-time flash
High pressure eror (ball valve closed)
38RUN light (10's digit): 3-time flash
TIMER light (1's digit): 8-time flash
Occurrence conditions: −55°C or lower is detected for 5 seconds continuously 3 times within 40 minutes after initial detection of this anomalous temperature. Or −55°C higher is detected for 5 seconds continuously within 20 seconds after power ON
Error display: (3 times)
Outdoor air temperature sensor is abnormal
39RUN light (10's digit): 3-time flash
TIMER light (1's digit): 9-time flash
Occurrence conditions: −25°C or lower is detected for 5 seconds continuously 3 times within 40 minutes after initial detection of this anomalous temperature
Error display: (3 times)
Discharge pipe sensor is abnormal (anomalous stop)
40RUN light (10's digit): 4-time flash
TIMER light (1's digit): OFF
Error display: (2 times)
Service valve (gas side) closed operation
41RUN light (10's digit): 4 time flash
TIMER light (1's digit): 1 time flash
RUN lamp (tens place): Flash 4 times
TIMER lamp (ones place): Flash 1 time
Cooling overload 1 (outdoor temp. 36~40℃)
42RUN light (10's digit): 4 time flash
TIMER light (1's digit): 2 time flash
Occurrence conditions: Compressor start fails 42 times in succession and the reason for the final failure is current cut
Error display: (2 times)
Current cut
43RUN light (10's digit): 4 time flash
TIMER light (1's digit): 3 time flash
RUN lamp (tens place): Flash 4 times
TIMER lamp (ones place): Flash 3 times
Cooling overload 2 (outdoor temp. 40~45℃)
44RUN light (10's digit): 4 time flash
TIMER light (1's digit): 4 time flash
RUN lamp (tens place): Flash 4 times
TIMER lamp (ones place): Flash 4 times
Heating overload 2 (outdoor temp. 12~17℃)
45RUN light (10's digit): 4 time flash
TIMER light (1's digit): 5 time flash
RUN lamp (tens place): Flash 4 times
TIMER lamp (ones place): Flash 5 times
Cooling overload 3 (outdoor temp. 45~℃)
46RUN light (10's digit): 4 time flash
TIMER light (1's digit): 6 time flash
RUN lamp (tens place): Flash 4 times
TIMER lamp (ones place): Flash 6 times
Heating overload 3 (outdoor temp. 17~℃)
47RUN light (10's digit): 4-time flash
TIMER light (1's digit): 7-time flash
Active filter voltage error
48RUN light (10's digit): 4-time flash
TIMER light (1's digit): 8-time flash
Error display: (3 times)
Outdoor unit's fan motor is abnormal
50RUN light (10's digit): 5 time flash
TIMER light (1's digit): OFF
Error display: ◯ (2 times)
RUN lamp (tens place): Flash 5 times
125℃ (compressor over heat)
51RUN light (10's digit): 5-time flash
TIMER light (1's digit): 1-time flash
Short circuit in the power transistor (high side) / Current cut circuit breakdown
57RUN light (10's digit): 5-time flash
TIMER light (1's digit): 7-time flash
Error display: (3 times)
Refrigeration cycle system protective control
58RUN light (10's digit): 5-time flash
TIMER light (1's digit): 8-time flash
Current safe
59RUN light (10's digit): 5-time flash
TIMER light (1's digit): 9-time flash
Compressor wiring is unconnection / Voltage drop / Low speed protective control
60RUN light (10's digit): 6 time flash
TIMER light (1's digit): OFF
Error display: (2 times)
RUN lamp (tens place): Flash 6 times
Rotor lock
61RUN light (10's digit): 6 time flash
TIMER light (1's digit): 1 time flash
RUN lamp (tens place): Flash 6 times
TIMER lamp (ones place): Flash 1 time
Connection lines between the indoor and outdoor units are faulty
62RUN light (10's digit): 6 time flash
TIMER light (1's digit): 2 time flash
Error display: ◯ (3 times)
RUN lamp (tens place): Flash 6 times
Serial transmission error
70RUN light (10's digit): 7 time flash
TIMER light (1's digit): OFF
Error display: ◯ (2 times)
Rotor lock
71RUN lamp (tens place): Flash 7 times
TIMER lamp (ones place): Flash 1 time
Rotor lock: below 16 rps
72RUN lamp (tens place): Flash 7 times
TIMER lamp (ones place): Flash 2 times
Rotor lock: above 16 rps
73RUN lamp (tens place): Flash 7 times
TIMER lamp (ones place): Flash 3 times
Poor phase position switching (U phase)
74RUN lamp (tens place): Flash 7 times
TIMER lamp (ones place): Flash 4 times
Poor phase position switching (V phase)
75RUN lamp (tens place): Flash 7 times
TIMER lamp (ones place): Flash 5 times
Poor phase position switching (W phase or not determined)
76RUN light (10's digit): 7 time flash
TIMER light (1's digit): 6 time flash
Occurrence conditions: When compressor start fails 42 times in succession and the reason for the final failure is rotor lock
Error display: ◯ (2 times)
Start of compressor program (within 4 sec. after phase position switching)
80RUN light (10's digit): 8 time flash
TIMER light (1's digit): OFF
RUN lamp (tens place): Flash 8 times
TIMER lamp (ones place): Off
Error of fan motor of indoor unit
81RUN light (10's digit): 8 time flash
TIMER light (1's digit): 1 time flash
Error display: ◯ (4 times)
RUN lamp (tens place): Flash 8 times
Vent-pipe sensor error (abnormal stop)
82RUN light (10's digit): 8 time flash
TIMER light (1's digit): 2 time flash
RUN lamp (tens place): Flash 8 times
TIMER lamp (ones place): Flash 2 times
Indoor heat exchanger sensor is abnormal (anomalous stop)
83RUN light (10's digit): 8 time flash
TIMER light (1's digit): 3 time flash
RUN lamp (tens place): Flash 8 times
TIMER lamp (ones place): Flash 3 times
Heat exchanger liquid pipe sensor error (abnormal stop)
84RUN light (10's digit): 8 time flash
TIMER light (1's digit): 4 time flash
RUN lamp (tens place): Flash 8 times
TIMER lamp (ones place): Flash 4 times
Anti-condensation control
85RUN light (10's digit): 8 time flash
TIMER light (1's digit): 5 time flash
RUN lamp (tens place): Flash 8 times
TIMER lamp (ones place): Flash 5 times
Anti-frost control
86RUN light (10's digit): 8 time flash
TIMER light (1's digit): 6 time flash
RUN lamp (tens place): Flash 8 times
TIMER lamp (ones place): Flash 6 times
High pressure control
87RUN light (10's digit): 8 time flash
TIMER light (1's digit): 7 time flash
RUN lamp (tens place): Flash 8 times
TIMER lamp (ones place): Flash 7 times
Compressor over heat protection control
88RUN light (10's digit): 8 time flash
TIMER light (1's digit): 8 time flash
Refrigeration cycle system protective control
E1Receiver Unit Red LED: -
Indoor Circuit Board Red LED: Stays Off
Indoor Circuit Board Green LED: Keeps Flashing
Outdoor Circuit Board Red LED: Stays Off
Indoor circuit board fault
E2Receiver Unit Red LED: -
Indoor Circuit Board Red LED: Stays Off
Indoor Circuit Board Green LED: Keeps Flashing
Outdoor Circuit Board Red LED: Stays Off
Indoor unit address: duplication of indoor unit number when addressing with the remote…
E3Receiver Unit Red LED: -
Indoor Circuit Board Red LED: Flashes twice
Indoor Circuit Board Green LED: Keeps Flashing
Outdoor Circuit Board Red LED: Stays Off
Outdoor unit power
E4Receiver Unit Red LED: Keeps Flashing
Indoor Circuit Board Red LED: Flashes Once
Indoor Circuit Board Green LED: Keeps Flashing
Outdoor Circuit Board Red LED: Stays Off
Incorrect address
E5Receiver Unit Red LED: Keeps Flashing
Indoor Circuit Board Red LED: Flashes Twice
Indoor Circuit Board Green LED: Keeps Flashing
Outdoor Circuit Board Red LED: Flashes Twice
Interconnecting cable
E6Receiver Unit Red LED: -
Indoor Circuit Board Red LED: Flashes Once
Indoor Circuit Board Green LED: Keeps Flashing
Outdoor Circuit Board Red LED: Stays Off
Indoor coil sensor
E7Receiver Unit Red LED: -
Indoor Circuit Board Red LED: Flashes Once
Indoor Circuit Board Green LED: Keeps Flashing
Outdoor Circuit Board Red LED: Stays Off
Indoor return air sensor
E8Receiver unit Red LED: Keeps Flashing
Indoor circuit board Red LED: Flashes Once
Indoor circuit board Green LED: Keeps Flashing
Outdoor circuit board Red LED: Stays Off
Abnormality of the heat exchanger sensor input
E9Receiver unit Red LED: -
Indoor circuit board Red LED: Flashes Once
Indoor circuit board Green LED: Keeps Flashing
Outdoor circuit board Red LED: Stays Off
Drain motor [DM] failure (drain motor open circuit or the drain motor is disconnected from…
E10Receiver unit Red LED: -
Indoor circuit board Red LED: Stays Off
Indoor circuit board Green LED: Keeps Flashing
Outdoor circuit board Red LED: Stays Off
17 or more indoor units are connected to one remote controller (maximum permitted: 16…
E11Receiver unit Red LED: -
Indoor circuit board Red LED: Stays Off
Indoor circuit board Green LED: Keeps Flashing
Outdoor circuit board Red LED: Stays Off
More than one indoor unit is connected to a remote controller while trying to address the…
E12Indoor circuit board Red LED: Flashes once
Indoor circuit board Green LED: Keeps Flashing
Outdoor circuit board Red LED: Stays Off
Outdoor circuit board Green LED: Keeps Flashing
While trying to auto address, one or more of the units (either indoor or outdoor) is not…
E14Receiver unit Red LED: -
Indoor circuit board Red LED: -
Indoor circuit board Green LED: -
Outdoor circuit board Red LED: -
Incorrect setting of SW2 on indoor unit PCB when setting up a master / slave system.…
E16Flashes Twice column: Stays off
Keeps Flashing column: Keeps Flashing
Flashes Twice (2nd) column: Stays off
Keeps Flashing (2nd) column: Keeps Flashing
Faulty indoor fan motor
E28Receiver unit Red LED: -
Indoor circuit board Red LED: Stays Off
Indoor circuit board Green LED: Keeps Flashing
Outdoor circuit board Red LED: Stays Off
Failure of the sensor within the remote controller
E30Receiver unit Red LED: -
Indoor circuit board Red LED: Stays Off
Indoor circuit board Green LED: Keeps Flashing
Outdoor circuit board Red LED: Flashes once
Indoor/outdoor unit connected error
E31LED 1: -
LED 2: Stays Off
LED 3: Keeps Flashing
LED 4: 8 Time Flash
Outdoor unit address fault
E32LED 1: -
LED 2: Stays Off
LED 3: Keeps Flashing
LED 4: Flashes Once
Outdoor unit power supply phase fault
E33LED 1: Keeps Flashing
LED 2: Stays Off
LED 3: Keeps Flashing
LED 4: Flashes Once
Compressor current abnormally high or open phase
E34LED 1: Keeps Flashing
LED 2: Stays Off
LED 3: Keeps Flashing
LED 4: Flashes Twice
Compressor current abnormally low (or no current) on L3, or open phase on L3
E35LED 1: -
LED 2: Stays Off
LED 3: Keeps Flashing
LED 4: Flashes Once
Compressor discharge gas temperature abnormally high
E36LED 1: -
LED 2: Stays Off
LED 3: Keeps Flashing
LED 4: Flashes once
Compressor discharge temperature abnormally high
E37LED 1: -
LED 2: Stays Off
LED 3: Keeps Flashing
LED 4: Flashes once
Outdoor heat exchanger sensor [ThOR] defective (open circuit) or poor sensor connection
E38Display 3: Keeps Flashing
Display 4: Keeps Flashing
Display 5: Keeps Flashing
Display 1: Keeps Flashing (red row)
Outdoor air sensor
E39Display 1: Keeps Flashing
Display 3: Keeps Flashing
Display 4: Flashes Once
Display 5: Keeps Flashing
Compressor discharge temperature sensor
E40Display 3: Keeps Flashing
Display 4: Flashes Once
Display 5: Keeps Flashing
Display 4: Flashes 3 Times
High pressure switch
E41Display 3: Keeps Flashing
Display 4: Flashes once
Display 5: Keeps Flashing
LED 1: Stays Off
Inverter power transistor
E42Display 3: Keeps Flashing
Display 4: Flashes once
Display 5: Keeps Flashing
LED 1: Stays Off
Compressor current
E43Display 3: Keeps Flashing
Display 4: Flashes once
Display 5: Keeps Flashing
LED 1: Stays Off
Number of indoor units
E45Display 3: Keeps Flashing
Display 4: Flashes once
Display 5: Keeps Flashing
LED 1: Stays Off
Inverter wiring
E46Display 3: Keeps Flashing
Display 4: Flashes once
Display 5: Keeps Flashing
LED 1: Stays Off
Address setting
E47LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
Inverter over voltage
E48LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
DC Outdoor Fan motor fault
E49LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
Low voltage detected
E51LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
Inverter PCB fault
E53LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
Suction pipe thermistor (Tho-S) disconnected
E54LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
Low pressure sensor (PSL) disconnected/output error
E55LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
Compressor under dome thermistor disconnected
E56LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
Power transistor thermistor faulty or disconnected (FDCVA151-251)
E57LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
Indoor heat exchanger sensor
E58lamp_2: Keeps Flashing
lamp_3: 1 to 5 times flash
lamp_4: Keeps Flashing
lamp_col_2: Keeps Flashing
Compressor start-up error
E59LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: 1 to 5 times flash
LED 4: Keeps Flashing
Compressor start-up error
E60LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once or twice
LED 4: Keeps Flashing
Compressor position detection error
E63LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
Emergency stop of indoor unit
E37-1LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: One time Flash
LED 4: Keeps Flashing
Outdoor heat exch thermistor failure (Tho-R1)
E37-2LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Two time Flash
LED 4: Keeps Flashing
Outdoor heat exch thermistor failure (Tho-R2)
E37-3LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Three time Flash
LED 4: Keeps Flashing
Outdoor heat exch thermistor failure (Tho-R3)
E37-4LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Four time Flash
LED 4: Keeps Flashing
Outdoor heat exch thermistor failure (Tho-R4)
E37-5LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Five time Flash
LED 4: Keeps Flashing
Outdoor heat exch thermistor failure (Tho-SC)
E37-6LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Six time Flash
LED 4: Keeps Flashing
Outdoor heat exch thermistor failure (Tho-H)
E54-1LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes once
LED 4: Keeps Flashing
Low pressure sensor (PSL) disconnection/output error
E54-2LED 1: Stays Off
LED 2: Keeps Flashing
LED 3: Flashes twice
LED 4: Keeps Flashing
High pressure sensor (PSH) disconnection/output error
NO INDICATIONReceiver Unit Red LED: -
Indoor Circuit Board Red LED: Stays Off
Indoor Circuit Board Green LED: Stays Off
Outdoor Circuit Board Red LED: Stays Off
Mains power: no mains power detected or T phase wire open
LED:RUN=1-TIME FLASH,TIMER=ONIndoor RUN light: 1-time flash
Indoor TIMER light: ON
Display (flashing) condition: When a heat exchanger temperature sensor 1 wire disconnection is detected while operation is stopped. (If a temperature of -28ºC or lower is detected for 15 seconds, it is judged that the wire is disconnected.) (Not displayed during operation.)
Heat exchanger temperature sensor 1 error
LED:RUN=2-TIME FLASH,TIMER=ONIndoor RUN light: 2-time flash
Indoor TIMER light: ON
Display (flashing) condition: When a room temperature sensor wire disconnection is detected while operation is stopped. (If a temperature of -45ºC or lower is detected for 15 seconds, it is judged that the wire is disconnected.) (Not displayed during operation.)
Room air temperature sensor error
LED:RUN=3-TIME FLASH,TIMER=ONIndoor RUN light: 3-time flash
Indoor TIMER light: ON
Display (flashing) condition: When a heat exchanger temperature sensor 2 wire disconnection is detected while operation is stopped. (If a temperature of -28ºC or lower is detected for 15 seconds, it is judged that the wire is disconnected.) (Not displayed during operation.)
Heat exchanger temperature sensor 2 error
LED:RUN=4-TIME FLASH,TIMER=ONIndoor RUN light: 4-time flash
Indoor TIMER light: ON
Display (flashing) condition: When normal data cannot be received from wireless LAN interface for two minutes continuously
Trouble of wireless LAN interface
LCD FLASHES CONTINUOUSLY OR OFFIndoor Red LED: Stays Off
Indoor Green LED: Keeps Flashing
Outdoor Red LED: Flashes Twice
Outdoor Green LED: Keeps Flashing
Open circuit or poor indoor/outdoor interconnecting wiring

Guides